.1 Provide means for addition, deletion, definition and modification of points and point types through the
operator interface..2 Provide links in the database such that if a point name is changed in database, all database occurrences
of that point will automatically be changed..3 Provide direct keyboard override of all physical and virtual points with an indication on the display of any
point that is operating under a keyboard override..4 The database for each physical or virtual point must only require definition once, regardless of the number of
locations where it is used.
Provide the following:
.1 Operator defined digital and analogue alarms including operator defined limits and differentials from set
points..2 Auto lockout of alarms when alarmed system is commanded off.
.3 Auto display of operator defined alarm messages.
.4 Operator defined routing of alarms.
.5 Log of points in alarm.
.1 User defined start/stop time or continuous trending.
.2 Sampling period user-adjustable from 5 seconds to 24 hours as a minimum.
.3 Change of value or change of state initiated.
.4 Display and print a minimum of 4 points simultaneously across the page.
.5 Ability to automatically dump trend logs to disk in ASCII format.
.1
Capability for display of a minimum of 4 points simultaneously, both
analog and digital on the same
graph.
.2 Capability for auto-scaling and ability to manually control horizontal and vertical scales.
.1 Provide the capability to accumulate units of all analog and digital points.
.1
Weekly - 20 minimum per SAP
-
time of day, day
-
weekend, alternate day
-
direct override by Annual Schedules
-
8 daily stops/starts per day
.2 Annual
- 6 minimum per SAP
-
entire calendar year available
.1 Analog Points
.2 Digital Points
.1 Provide controllers, resident in each SAP and/or TUC, including a three-term, proportional, integral,
derivative, (PID) control algorithm..2 Provide, in each controller, the following set up and tuning capabilities:
.1 Direct or reverse acting.
.2 Output value to control, 0 to 100%.
.3 Set point.
.4 Proportional Gain.
.5 Integral gain.
.6 Derivative gain.
.7 Sampling time - variable from 1 to 60 seconds.
.8 Control loop bias..3 Provision shall exist for the modification of the above by OCL programs and/or the operator while on-line
through a terminal.
.1 The stand alone panels (SAPs) and soft terminal unit controllers (TUCs) shall have the capability for the
operator to develop and run custom application programs. For this, the system shall have a proven OCL
which shall be capable of reading the value and/or status of all system points and initiating both digital and
analog control actions from any user defined combination of calculations and logical expressions which
shall at a minimum include:- Addition, subtraction, multiplication and division;
- Square roots, summations, absolute differences;
- Logical ``not'', ``and'', ``or'', ``nor'', ``and'', ``less than'', ``greater than'', and ``equal to'' or their
logical equivalents;
- Time delays in seconds, minutes or hours;
- Ability to embed comments in system generated documentation;
- Ability to use time-of-day and day-of-year in algebraic calculations; and
- Ability to use weekly and annual schedules..2 Provide code for the following control strategies:
.1 If real time is between 8:00 AM and 4:00 PM and minimum space temperature is more than
0.5 deg C below the building objective temperature, then start Pump #1..2 As soon as Pump #1 has been on for 10 minutes, turn on the boiler.
.3 If day of the year is before July 2, then factor A is equal to 0.1667 - (July 2 - day of year)/1368,
otherwise the factor A is equal to 0.1661 - (day of year - July 2)/1368..4 Seclect high of space temperature #2, space temperature #3 and space temperature #6.
.5 If the real time is greater than 8:00 AM minus a factor, times the difference between the setpoint
and space temperature and if the real time is less than 3:30 PM and if outside air temperature is
less than 10 deg C, then enable boiler.
.1 Provide a full screen editor to enable editing of the OCL programs source code down to character by
character changes..2 Provide the capability in the editor of accepting programs from ASCII files that have been created on
other MS-DOS compatible computers and word processors..3 If a point is removed from the database, show an error signal for undefined character on the appropriate
line whenever a program using that point is viewed, edited or printed.