CCS PERFORMANCE SPECIFICATIONS SECTION 15940

PS 4 - INTRA-SYSTEM COMMUNICATION

4.1    Network Communications

.1    Stand-Alone Panels (SAPs)

       .1    Provide a fully networked system of SAPs which use a peer-to-peer communications protocol to
              support the distributed control features as specified herein. Each SAP shall be connected directly to
              the network. Each SAP shall have equal network access priority and shall not require a separate
              interface panel (gateway) to accomplish network communications.

      .2    Provide a means to ensure communication integrity. Provide detail of your system with proposal.

      .3    To prevent damage to the system each data highway line shall be provided with a means of isolation,
             either optically or by some other means.  Provide detail of your protection system with proposal.

      .4    Upon failure of the network to communicate information from one SAP to other SAPs, retain the last
             legitimate value of each point in the SAPs that require it, and continue to control the systems based on
             those values. Failure of any SAP, or any part of a SAP on the network, shall not affect the ability of the
             network to communicate among the remaining SAPs.

      .5    Each physical or virtual point shall have a user-definable, unique, system-wide logical point mnemonic.
             The format of this point mnemonic shall conform to BCBC Point Naming Convention. All point functions
             such as commands, overrides, trends, reports, logs and graphics shall only need to use this unique logical
             point mnemonic.

      .6    Values, status's and attributes of physical and software points from one SAP shall be available for use in
             any other SAPs. Any broadcast points, send-receive blocks or any other form of table or database that
             is required to initialize and accomplish this function shall be created solely, and automatically, by the
             operating system, without the need for operator intervention. Listings of physical and software points
             shall not include tables referred to in this paragraph.

.2    Terminal Unit Controllers (TUCs)

       For systems which include terminal unit controllers (TUC's).

       .1    TUC's shall be considered to be any panel connected to a sub-communication network, where access
              to the features and points of the TUC is only obtainable through the SAP to which the sub-network is
              connected. TUCs shall have a limited number of inputs and outputs, which are specifically designed to
              control one component serving a single thermostatic zone (e.g., VAV terminal unit, dual-duct terminal
              unit, fan-coil unit, zone heat pump, etc.).

       .2    The terminal unit controllers (TUCs) shall incorporate all of the requirements for the stand-alone panels
              (SAPs), except for peer to peer communications (
PS 4.1.1.1) and auto-networking provisions
              (PS 4.1.1.6).

       .3    The auto-networking requirements defined in PS 4.1.1.6 for SAPs apply between the TUC and the
              SAP it is connected to. If the TUC is connected to the main peer to peer communication network,
              the full requirements of PS 4.1.1.6 apply.

4.2    System Display and Processing Speed

.1    For multi SAP systems, the system processing speed is intended to address inter-SAP communications
       and will be checked during the commissioning phase by evaluating value updates from one SAP as received
       and displayed in another SAP. This will be done by setting up a display of all SAP counters and checking
       how frequently each counter is updated on the refreshed display on site.

.2    Every counter shall show an updated value on the display within TWENTY (20) seconds of the previous
       update value appearing. Provide confirmation with Proposal that required system processing speed will be
       achieved.