[ Previous Page || Table of Contents || Overview || Section TOC || Next Page ]


The information displayed here is available as a Microsoft Word.doc file. Please click on this link to download this file.


CCS PERFORMANCE SPECIFICATIONS SECTION 15940

PS 6 - FIELD DEVICES

6.1    General

        .1    This Clause contains a comprehensive range of field devices listed alphabetically by ``Point type'' code, not all of
               which will necessarily be applicable to this project. Refer to the ``Point Type'' column on the points lists in Section
               15930 to identify the devices relevant to this project

        .2    Some point types have a number as the last character in order to identify variations in a group of similar field devices.
               For each separate point type or group of similar devices (common point type except for number) all items provided
               shall be the product of one manufacturer.

        .3    All field devices shall be selected to have full compatibility with the SAPs, TUCs or other controls components being
               proposed.

        .4    Any field device proposed for use which is not one of the products listed under ``Standard of Acceptance'' will be
               evaluated by the Owner's representative against the specified technical performance and the quality and
               characteristics of the products which are listed. If any proposed field device is deemed not equivalent to the
               specification, then the controls contractor shall provide another device which does meet specification at no extra
               cost.

        .5    The shop drawing submittal shall include technical data for all field devices listed in the points lists, specifically
               cross-referenced to the particular point type to facilitate the shop drawing review.

        .6    Some devices may require different ranges, capacities, etc. in particular applications, even though the device or
               component is otherwise the same. Where definition of such variations is required in the specifications or points lists,
               the point type will use suffixes, for example ``DPS/x'' or ``DA1/x''. The suffixes are explained in the ``Technical
               Performance'' portion of each point type specification.

        .7    The end-to-end accuracy required for analog devices shall include the combined effect of sensitivity, hysteresis,
               linearity and repeatability between the measured variable and the output at the operator interface device, or between
               the panel signal to the digital-to-analog converter and the controlled variable.

        .8    Devices shall meet the specific requirements listed, and shall be compatible with respect to power supply, signal
               characteristics, or other factors with the CCS being proposed. Power supplies shall be provided as required for any
               and all devices.

6.2    Point Type ``CRS''

        .1    Description - Control Relay Status ``CRS'' is used where the field device will be either:

     -    an auxiliary dry contact, supplied as part of the equipment whose status will be monitored by this point, or

     -    if there is no auxiliary dry contact on the equipment, a relay as specified in 2. and 3., provided by the
         control contractor.

        .2    Technical Performance - a high impedance relay to produce a dry contact.

        .3    Standard of Acceptance      - Omron Model GSD
                                                         - Veris Model 607 voltage bug.

6.3    Point Type ``CR1''

        .1    Description - Control Relay (Solid State)

        .2    Technical Performance - 240V, 10 amp capacity. SPST function. Normally open (or normally closed) as required
               by points list or application complete with optical isolation. Suitable for switching inductive AC loads.

        .3    Standard of Acceptance      - Electromatic - RS104240
                                                         - Potter & Brumfield EOTZ Series.
                                                         - Grayhill 7052-04-C-12-S.

6.4    Point Type ``CR2''

        .1    Description - Control relay (dry contact electro-mechanical relay).

        .2    Technical Performance - 240V, 10A to suit application.

        .3    Standard of Acceptance      - IDEC-RH Series
                                                         - Johnson R1020 series.

6.5    Point Type ``CR3''

        .1    Description - Control relay (Solid state relay suitable for switching D.C. loads).

        .2    Technical Performance - 60 VDC.

        .3    Standard of Acceptance      - Grayhill.

6.6    Point Type ``CS1''

        .1    Description - Current sensor (analogue).

        .2    Technical Performance - Self powered, with insertion impedance loss less than 0.0006 ohms under all conditions.
               End-to-end accuracy +/- 2% of full scale at each range. Ranges:
1.0 to 10.0 amps, low; 5 to 50 amps, middle; 20
               to 200 amps, high; selectable by switch or by setting jumpers.

        .3    Standard of Acceptance      - Greystone CS-150.

6.7    Point Type ``CS2''

        .1    Description - Current Sensor (switch).

        .2    Technical Performance - Solid State N.O. AC switch. Same ranges as point type ``CS1''. Manual adjustment of
               switch threshold setting.

        .3    Standard of Acceptance      - Greystone CS-125.

6.8    Point Type ``CV1''

        .1    Description - Control Valve (2 way, 2 position)

        .2    Technical Performance - Brass or bronze globe valve construction, with screwed ends. Materials suitable for chilled
               water or hot water up to 125 deg C 24 VAC. Working pressure, 875 kPa. N.O. spring return. Minimum close off
               pressure rating shall meet requirements in the points lists; if no requirement, minimum close off pressure rating shall
               be 70 kPa.

        .3    Standard of Acceptance      - Honeywell V8043 series
                                                         - Johnson J-series

        .4    Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific Cv is
               specified in the points list or on a valve schedule, ensure the control valve proposed has a similar Cv to that
               specified.

6.9    Point Type ``CV2''

        .1    Description - Control Valve (2 way, floating control).

        .2    Technical Performance - Brass or bronze body, globe valve with equal percentage flow characteristic, screwed
               ends. Materials suitable for chilled water or hot water up to 125 deg C. Working pressure 875 kPa. 24 VAC
               reversing motor drive. Minimum close off pressure rating shall be 30 psi, or as stated in the points list, which ever
               is higher.

        .3    Standard of Acceptance     - Johnson
                                                        - Honeywell

        .4    Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific Cv is
               specified in the points list or on a valve schedule, ensure the control valve proposed has a similar Cv to that
               specified.

6.10  Point Type ``CV3''

        .1    Description - Control Valve (2 way modulating, non-spring-return).

        .2    Technical Performance - Globe valve body, with equal percentage flow characteristics. Materials suitable for chilled
               water or hot water up to 125 deg C. Modulating actuator with 0-10 VDC signal range, power to open and power
               to close. Working pressure 875 kPa.

        .3    Standard of Acceptance     - Johnson
                                                        - Honeywell

        .4    Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific Cv is
               specified in the points list or on a valve schedule, ensure the control valve proposed has a similar Cv to that
               specified.

6.11  Point Type ``CV4''

        .1    Description - Control Valve (2 way, modulating, spring return).

        .2    Technical Performance - Technical performance shall be as specified in 6.10.2.

        .3    Standard of Acceptance     -  Johnson
                                                         - Honeywell

        .4    Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific Cv is
               specified in the points list or on a valve schedule, ensure the control valve proposed has a similar Cv to that
               specified.

6.12  Point Type ``DA1/x''

        .1    Description - Damper Actuator (Electric, modulating, non-spring-return).

        .2    Technical Performance         - Power Voltage 24 VAC or 120 VAC.
                                                          - Control Voltage 0 - 10 VDC.

     Suffixes    -    ``DA1/A''       - 50 in-lb torque capacity.
                     -     ``DA1/B''      - 90 in-lb torque capacity.
                     -     ``DA1/C''      - 130 in-lb torque capacity.

        .3    Standard of Acceptance       - Belimo NM-24SR or NM-24SRS (``DA1/A'')
                                                          - Belimo SMC-24SR (``DA1/B'')
                                                          - Belimo SM-24SR or SM-24SRS (``DA1/C'')
                                                          - Johnson Controls M140-GGA (``DA1/A'')
                                                          - Johnson Controls M150-GGA (DA1/B'' or ``DA1/C'')

6.13  Point Type ``DA2/x''

        .1    Description - Damper Actuator (Electric, modulating, spring return).

        .2    Technical Performance         - Power voltage 24 VAC or 120 VAC
                                                          - Control Voltage 0 - 10 VDC

               Suffixes     -    ``DA2/A''      - 50 in-lb torque capacity.
                               -     ``DA2/B''      - 90 in-lb torque capacity.

        .3    Standard of Acceptance       - Belimo NF-24SR (``DA2/A'')
                                                          - Belimo AF24-SR ("DA2/B & C")
                                                          - Johnson Controls M130-GGA (``DA2/A'' only)

6.14  Point Type ``DA3/x''

        .1    Description - Damper Actuator (Electric, 2-position, non-spring-return).

        .2    Technical Performance - Power Voltage 24 VAC or 120 VAC

               Suffixes     -    ``DA3/A''      - 50 in-lb torque capacity.
                               -     ``DA3/B''      - 90 in-lb torque capacity.
                               -     ``DA3/C''      - 130 in-lb torque capacity.

       .3    Standard of Acceptance       - Belimo NM-24 (``DA3/A'')
                                                          - Belimo SMC-24 (``DA3/B'')
                                                          - Belimo SM-24 (``DA3/C'')

6.15  Point Type ``DA4/x''

        .1    Description - Damper Actuator (Electric, 2-position, spring return).

        .2    Technical Performance - Power Voltage, 24 VAC or 120 VAC.

               Suffixes     -    ``DA4/A''       - 130 in-lb torque capacity.

        .3    Standard of Acceptance        - Belimo SF-24, AF-24, SF-120, NF-120.

6.16  Point Type ``DDC''

        .1    Description - Point type ``DDC'' is used to describe on analog output which is to be connected to a piece of
               equipment not supplied by the controls contractor for the purpose of controlling that equipment's operation in some
               way. Examples would be an output to a variable speed drive to control its speed, or an output to a modulating chiller
               (or boiler) to control its operating output.

        .2    The controls contractor shall provide wiring, and interface devices.

6.17  Point Type ``DHS''

        .1    Description - Duct mounted relative humidity sensor.

        .2    Technical Performance - Operating range, 10% RH to 90% RH, over a 0 deg C to 60 deg C temperature range.
               End-to-end accuracy +/- 3% of operating range, with maximum temperature dependence of
0.2% per deg C
               change. 200 mm long probe, with enclosure, for mounting in duct.

        .3    Standard of Acceptance         - Greystone HS-250-C-02
                                                            - Hy-cal CT-829-A

6.18  Point Type ``DPS/x''

        .1    Description - Differential Pressure Sensor

        .2    Technical Performance - Solid-state design, operating on capacitance principle, with non-interactive fine resolution,
               zero, and span adjustments. End-to-end accuracy +/- 2% of full scale pressure range, including temperature
               compensation. Shall have integral filters at each air connection port.

               Suffixes     -    ``DPS/A''          - 0 to 25 PA pressure range.
                               -     ``DPS/B''         - 0 to 50 PA pressure range.
                               -     ``DPS/C''         - 0 to 75 PA pressure range.
                               -     ``DPS/D''         - 0 to 125 PA pressure range.
                               -     ``DPS/E''          - 0 to 250 PA pressure range.
                               -     ``DPS/F''          - 0 to 500 PA pressure range.
                               -     ``DPS/G''         - 0 to 750 PA pressure range.
                               -     ``DPS/H''         - 0 to 1250 PA pressure range.

            .3     Standard of Acceptance      - Modus T20-xxx, T30-xxx, or T40-xxx to suit pressure range and application.
                                                              - Autotran 700.

6.19  Point Type ``DTS1/x''

        .1    Description - Duct temperature sensor, with an averaging element.

        .2    Technical Performance - Constructed of FT6 plenum rated cable or soft copper tubing, incorporating numerous
               temperature sensors encapsulated at equal distances along the length of the element. The assembly acts as a single
               sensor, reporting the average temperature from all the individual sensors. Operating range: 0 deg C to 60 deg C;
               end-to-end accuracy +/-
0.3 deg C. Assembly complete with wiring housing and mounting flange.

               Suffixes     -    ``DTS1/A''       - 3.5 m sensor cable length
  
                            -     ``DTS1/B''       - 6.0 m cable length

        .3    Standard of Acceptance         - Greystone TE-200
                                                            - Pre-con

6.20  Point Type ``DTS2''

        .1    Description - Duct temperature sensor, with probe type element.

        .2    Technical Performance - Sensor encapsulated in a 200 mm long, 6 mm OD copper or stainless steel probe.
               Operating range 0 deg C to 60 deg C; end-to-end accuracy +/-
0.3 deg C. Assembly complete with wiring housing
               and mounting flange.

        .3    Standard of Acceptance         - Greystone TE-200-B-7-C
                                                            - Pre-con

6.21  Point Type ``FRZ''

        .1    Description - ``Freezestat'' auto-reset , complete with auxiliary dry contact in order to provide a separate digital
               input to the DDC system.

        .2    Technical Performance - Range: -10 deg C to 15 deg C; probe length 6 m. Control responds to the lowest
               temperature along any
0.3 m of the entire length of the element.

        .3    Standard of Acceptance         - Penn A170-GA-1

6.22  Point Type ``GAS1''

        .1    Description - CO2 concentration sensor.

        .2    Technical Performance - 0 - 2500 ppm +/- 2% Full Scale.

        .3    Standard of Acceptance         - Quatrosense Environmental Ltd. QEL QTS - 2000.

6="6_23">6.23  Point Type ``GAS2''

        .1    Description - Carbon monoxide concentration sensor.

        .2    Technical Performance - 0 - 125 ppm CO output drift < 2% signal/month.

        .3    Standard of Acceptance        - Quatrosense Environmental Ltd.

6.24  Point Type ``GAS3''

        .1    Description - flammable gas concentration sensor.

        .2    Technical Performance -

        .3    Standard of Acceptance -

6.25  Point Type ``GAS4''

        .1    Description - Refrigerant vapour concentration sensor.

        .2    Technical Performance -

        .3    Standard of Acceptance -

6.26  Point Type ``GAS5''

        .1    Description - Total volatile organic compounds (TVOC's) concentration sensor, designed for mounting within an
               occupied space. This type of device is sometimes referred to as an indoor air quality sensor.

        .2    Technical Performance -

        .3    Standard of Acceptance -

6.27  Point Type ``LS1''

        .1    Description - Photocell light level sensor, with analogue output related to light intensity.

        .2    Technical Performance - Dark 1 meg ohm, bright 1.5 K ohm.

        .3    Standard of Acceptance      - Greystone PSR-1.

6.28  Point Type ``LS2''

        .1    Description - Photocell, adjustable light level switch.

        .2    Technical Performance -

        .3    Standard of Acceptance -

6.29  Point Type ``OS1''

        .1    Description - Passive infrared occupancy sensor.

        .2    Technical Performance -

        .3    Standard of Acceptance -

6.30  Point Type ``OTS''

        .1    Description - Outside air temperature sensor.

        .2    Technical Performance - 10K ohm thermistor sensor encapsulated in a 6 mm OD probe, complete with
               weatherproof enclosure, sun shield and mounting bracket. Operating range: -35 deg C to +50 deg C. End-to-end
               accuracy: +/-
0.3 deg C over the entire operating range.

        .3    Standard of Acceptance      - Greystone TE-200-F, c/w 100K ohm parallel resistor.

6.31  Point Type ``PS1''

        .1    Description - Pipe Pressure Transducer

        .2    Technical Performance - Brazed assembly with 300 series stainless steel parts that are in contact with the media,
               snap tract and circuit board c/w external pressure sensor and mounted in a NEMA 4 enclosure. Accuracy +/-
3.0%
               span from best fit straight line.

               Inputs     - 7.5 - 32 VDC

               Range     - Suffix A              - 350 kPa

        .3    Standard of Acceptance      - Greystone PGS-100

6.32  Point Type ``PTS1''

        .1    Description - Pipe Temperature Sensor, immersion type .

        .2    Technical Performance - 10K ohm thermistor sensor encapsulated in a 6 mm OD, 50 mm long probe, with screw
               fitting for insertion into a standard thermowell. Sensor assembly to be complete with enclosure and thermowell.
               Operating range: -10 deg C to 100 deg C. End-to-end accuracy: +/-
0.3 deg C over the entire operating range.

        .3    Standard of Acceptance      - Greystone TE-200-C

6.33  Point Type ``PTS2''

        .1    Description - Pipe Temperature Sensor, strap-on type.

        .2    Technical Performance - 10K ohm thermistor encapulated in a stainless steel pad designed for strap-on installation.
               Assembly to be complete with solid-state circuitry in an enclosure and connecting cable to the thermistor. Operating
               range: -10 deg C to 100 deg C. End-to-end accuracy: +/-
0.3 deg C over the entire operating range.

        .3    Standard of Acceptance      - Greystone TE-200-E-7

6.34  Point Type ``RHS''

        .1    Description - Relative Humidity Sensor Room Type.

        .2    Technical Performance - operating range: 10% RH to 90% RH, over a 0 deg C to 60 deg C temperature range.
               End-to-end accuracy: +/-
3.0% of operating range, with maximum temperature dependence of 0.2% RH per
               deg C change. Assembly shall be complete with a baseplate for wall mounting, a rigid circuit board for all circuitry
               and the sensing element, and a ventilated enclosure.

        .3    Standard of Acceptance      - Greystone HS-150-B-02
                                                         - Hy-cal C102-H

6.35  Point Type ``RTS1''

        .1    Description - Room temperature sensor complete with momentary override switch.

        .2    Technical Performance - Assembly shall consist of a 10K ohm thermistor and related circuitry mounted on a circuit
               board/baseplate for wall mounting, complete with a vented, plastic enclosure. Operating range: 10 deg C to 30 deg
               C. End-to-end accuracy: +/-
0.3 deg C over the entire operating range.

        .3    Standard of Acceptance      - Greystone TE-200-AE-OR

6.36  Point Type ``RTS2''

        .1    Description - Room Temperature Sensor, security type.

        .2    Technical Performance - Assembly shall consist of a 10K ohm thermistor and related circuitry mounted on a rigid,
               metal cover plate designed for mounting into a recessed junction box. The sensing element shall be attached directly
               to the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
0.3 deg C over the entire
               pressure range.

        .3    Standard of Acceptance      - Greystone TE-200-AS

6.37  Point Type ``RTS3''

        .1    Description - Room temperature sensor complete with momentary override switch, setpoint adjustment, and
               setpoint indication.

        .2    Technical Performance - Assembly shall consist of a 10K ohm thermistor and related circuitry mounted on a rigid,
               metal cover plate designed for mounting into a recessed junction box. The sensing element shall be attached directly
               to the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
0.3 deg C over the entire
               pressure range.

        .3    Standard of Acceptance      - Greystone TE-200-IT
                                                         - Delta Intellistat RTS406

6.38  Point Type ``VS1''

        .1    Description - Velocity sensor (single point flow sensor).

        .2    Technical Performance - 0 - 3000 FPM Adjustable 4'' - 16'' ducts. (Thermal anemometer technology).

        .3    Standard of Acceptance      - BELIMO.

6.39  Point Type ``VS2''

        .1    Description - Air velocity sensor with thermal anemometer technology, using differential pressure signal from a flow
               grid in duct or VAV box inlet.

        .2    Technical Performance -

        .3    Standard of Acceptance -

6.40  Point Type ``WPS''

        .1    Description - (Window Position Switch) Point type ``WPS'' is used to describe a digital input connected to a dry
               contact which is part of a magnetic proximity switch on openable sections of glazing. The dry contact will be open
               when the window is open, and closed when the window is closed.

        .2    If the window supplier provides the proximity switches, and wiring from their dry contacts, to 300 mm above the
               window head above the openable section, use the CRS designation for the point.


[ Previous Page || Table of Contents || Overview || Section TOC || Next Page ]

[ Comments || Disclaimer ]