[ Previous Page || Table of Contents || Overview || Section TOC || Next Page ]
The information displayed here is available as a Microsoft Word.doc file. Please click on this link to download this file.
.1 This Clause contains a
comprehensive range of field devices listed alphabetically by ``Point type'' code, not all
of
which
will necessarily be applicable to this project. Refer to the ``Point Type'' column on the
points lists in Section
15930
to identify the devices relevant to this project
.2 Some point types have a
number as the last character in order to identify variations in a group of similar field
devices.
For
each separate point type or group of similar devices (common point type except for number)
all items provided
shall
be the product of one manufacturer.
.3 All field devices shall
be selected to have full compatibility with the SAPs, TUCs or other controls components
being
proposed.
.4 Any field device
proposed for use which is not one of the products listed under ``Standard of Acceptance''
will be
evaluated
by the Owner's representative against the specified technical performance and the quality
and
characteristics
of the products which are listed. If any proposed field device is deemed not equivalent to
the
specification,
then the controls contractor shall provide another device which does meet specification at
no extra
cost.
.5 The shop drawing
submittal shall include technical data for all field devices listed in the points lists,
specifically
cross-referenced
to the particular point type to facilitate the shop drawing review.
.6 Some devices may
require different ranges, capacities, etc. in particular applications, even though the
device or
component
is otherwise the same. Where definition of such variations is required in the
specifications or points lists,
the
point type will use suffixes, for example ``DPS/x'' or ``DA1/x''. The suffixes are
explained in the ``Technical
Performance''
portion of each point type specification.
.7 The end-to-end accuracy
required for analog devices shall include the combined effect of sensitivity, hysteresis,
linearity
and repeatability between the measured variable and the output at the operator interface
device, or between
the
panel signal to the digital-to-analog converter and the controlled variable.
.8 Devices shall meet the
specific requirements listed, and shall be compatible with respect to power supply, signal
characteristics,
or other factors with the CCS being proposed. Power supplies shall be provided as required
for any
and
all devices.
.1 Description - Control Relay Status ``CRS'' is used where the field device will be either:
- an auxiliary dry contact, supplied as part of the equipment whose status will be monitored by this point, or
- if there is no auxiliary dry contact on the equipment, a relay as specified in 2. and 3., provided by the
control contractor.
.2 Technical Performance - a high impedance relay to produce a dry contact.
.3 Standard of Acceptance
- Omron Model GSD
-
Veris Model 607 voltage bug.
.1 Description - Control Relay (Solid State)
.2 Technical Performance -
240V, 10 amp capacity. SPST function. Normally open (or normally closed) as required
by
points list or application complete with optical isolation. Suitable for switching
inductive AC loads.
.3 Standard of Acceptance
- Electromatic - RS104240
-
Potter & Brumfield EOTZ Series.
-
Grayhill 7052-04-C-12-S.
.1 Description - Control relay (dry contact electro-mechanical relay).
.2 Technical Performance - 240V, 10A to suit application.
.3 Standard of Acceptance
- IDEC-RH Series
-
Johnson R1020 series.
.1 Description - Control relay (Solid state relay suitable for switching D.C. loads).
.2 Technical Performance - 60 VDC.
.3 Standard of Acceptance - Grayhill.
.1 Description - Current sensor (analogue).
.2 Technical Performance -
Self powered, with insertion impedance loss less than 0.0006 ohms
under all conditions.
End-to-end
accuracy +/- 2% of full scale at each range. Ranges: 1.0 to 10.0 amps,
low; 5 to 50 amps, middle; 20
to
200 amps, high; selectable by switch or by setting jumpers.
.3 Standard of Acceptance - Greystone CS-150.
.1 Description - Current Sensor (switch).
.2 Technical Performance -
Solid State N.O. AC switch. Same ranges as point type ``CS1''. Manual adjustment of
switch
threshold setting.
.3 Standard of Acceptance - Greystone CS-125.
.1 Description - Control Valve (2 way, 2 position)
.2 Technical Performance -
Brass or bronze globe valve construction, with screwed ends. Materials suitable for
chilled
water
or hot water up to 125 deg C 24 VAC. Working pressure, 875 kPa. N.O. spring return.
Minimum close off
pressure
rating shall meet requirements in the points lists; if no requirement, minimum close off
pressure rating shall
be 70
kPa.
.3 Standard of Acceptance
- Honeywell V8043 series
-
Johnson J-series
.4 Submittal Data -
Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is
specified
in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that
specified.
.1 Description - Control Valve (2 way, floating control).
.2 Technical Performance -
Brass or bronze body, globe valve with equal percentage flow characteristic, screwed
ends.
Materials suitable for chilled water or hot water up to 125 deg C. Working pressure 875
kPa. 24 VAC
reversing
motor drive. Minimum close off pressure rating shall be 30 psi, or as stated in the points
list, which ever
is
higher.
.3 Standard of Acceptance
- Johnson
-
Honeywell
.4 Submittal Data -
Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is
specified
in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that
specified.
.1 Description - Control Valve (2 way modulating, non-spring-return).
.2 Technical Performance -
Globe valve body, with equal percentage flow characteristics. Materials suitable for
chilled
water
or hot water up to 125 deg C. Modulating actuator with 0-10 VDC signal range, power to
open and power
to
close. Working pressure 875 kPa.
.3 Standard of Acceptance
- Johnson
-
Honeywell
.4 Submittal Data -
Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is
specified
in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that
specified.
.1 Description - Control Valve (2 way, modulating, spring return).
.2 Technical Performance - Technical performance shall be as specified in 6.10.2.
.3 Standard of Acceptance
- Johnson
-
Honeywell
.4 Submittal Data -
Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is
specified
in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that
specified.
.1 Description - Damper Actuator (Electric, modulating, non-spring-return).
.2 Technical Performance
- Power Voltage 24 VAC or 120 VAC.
-
Control Voltage 0 - 10 VDC.
.3 Standard of Acceptance
- Belimo NM-24SR or NM-24SRS (``DA1/A'')
-
Belimo SMC-24SR (``DA1/B'')
-
Belimo SM-24SR or SM-24SRS (``DA1/C'')
-
Johnson Controls M140-GGA (``DA1/A'')
-
Johnson Controls M150-GGA (DA1/B'' or ``DA1/C'')
.1 Description - Damper Actuator (Electric, modulating, spring return).
.2 Technical Performance
- Power voltage 24 VAC or 120 VAC
-
Control Voltage 0 - 10 VDC
Suffixes
- ``DA2/A'' - 50 in-lb
torque capacity.
-
``DA2/B'' - 90 in-lb torque capacity.
.3 Standard of Acceptance
- Belimo NF-24SR (``DA2/A'')
-
Belimo AF24-SR ("DA2/B & C")
-
Johnson Controls M130-GGA (``DA2/A'' only)
.1 Description - Damper Actuator (Electric, 2-position, non-spring-return).
.2 Technical Performance - Power Voltage 24 VAC or 120 VAC
Suffixes
- ``DA3/A'' - 50 in-lb
torque capacity.
-
``DA3/B'' - 90 in-lb torque capacity.
-
``DA3/C'' - 130 in-lb torque capacity.
.3 Standard of
Acceptance - Belimo NM-24 (``DA3/A'')
-
Belimo SMC-24 (``DA3/B'')
-
Belimo SM-24 (``DA3/C'')
.1 Description - Damper Actuator (Electric, 2-position, spring return).
.2 Technical Performance - Power Voltage, 24 VAC or 120 VAC.
Suffixes - ``DA4/A'' - 130 in-lb torque capacity.
.3 Standard of Acceptance - Belimo SF-24, AF-24, SF-120, NF-120.
.1 Description - Point
type ``DDC'' is used to describe on analog output which is to be connected to a piece of
equipment
not supplied by the controls contractor for the purpose of controlling that equipment's
operation in some
way.
Examples would be an output to a variable speed drive to control its speed, or an output
to a modulating chiller
(or
boiler) to control its operating output.
.2 The controls contractor shall provide wiring, and interface devices.
.1 Description - Duct mounted relative humidity sensor.
.2 Technical Performance -
Operating range, 10% RH to 90% RH, over a 0 deg C to 60 deg C temperature range.
End-to-end
accuracy +/- 3% of operating range, with maximum temperature dependence of 0.2% per deg C
change.
200 mm long probe, with enclosure, for mounting in duct.
.3 Standard of Acceptance
- Greystone HS-250-C-02
-
Hy-cal CT-829-A
.1 Description - Differential Pressure Sensor
.2 Technical Performance -
Solid-state design, operating on capacitance principle, with non-interactive fine
resolution,
zero,
and span adjustments. End-to-end accuracy +/- 2% of full scale pressure range, including
temperature
compensation.
Shall have integral filters at each air connection port.
Suffixes
- ``DPS/A''
- 0 to 25 PA pressure range.
-
``DPS/B'' - 0 to 50 PA
pressure range.
-
``DPS/C'' - 0 to 75 PA
pressure range.
-
``DPS/D'' - 0 to 125 PA
pressure range.
-
``DPS/E'' - 0 to
250 PA pressure range.
-
``DPS/F'' - 0 to
500 PA pressure range.
-
``DPS/G'' - 0 to 750 PA
pressure range.
-
``DPS/H'' - 0 to 1250
PA pressure range.
.3
Standard of Acceptance - Modus T20-xxx,
T30-xxx, or T40-xxx to suit pressure range and application.
-
Autotran 700.
.1 Description - Duct temperature sensor, with an averaging element.
.2 Technical Performance -
Constructed of FT6 plenum rated cable or soft copper tubing, incorporating numerous
temperature
sensors encapsulated at equal distances along the length of the element. The assembly acts
as a single
sensor,
reporting the average temperature from all the individual sensors. Operating range: 0 deg
C to 60 deg C;
end-to-end
accuracy +/-0.3 deg C. Assembly complete with wiring housing and
mounting flange.
Suffixes
- ``DTS1/A'' - 3.5 m sensor cable length
-
``DTS1/B'' - 6.0 m cable length
.3 Standard of Acceptance
- Greystone TE-200
-
Pre-con
.1 Description - Duct temperature sensor, with probe type element.
.2 Technical Performance -
Sensor encapsulated in a 200 mm long, 6 mm OD copper or stainless steel probe.
Operating
range 0 deg C to 60 deg C; end-to-end accuracy +/-
.3 Standard of Acceptance
- Greystone TE-200-B-7-C
-
Pre-con
.1 Description -
``Freezestat'' auto-reset , complete with auxiliary dry contact in order to provide a
separate digital
input
to the DDC system.
.2 Technical Performance -
Range: -10 deg C to 15 deg C; probe length 6 m. Control responds to the lowest
temperature
along any
.3 Standard of Acceptance - Penn A170-GA-1
6.22 Point Type ``GAS1''.1 Description - CO2 concentration sensor.
.2 Technical Performance - 0 - 2500 ppm +/- 2% Full Scale.
.3 Standard of Acceptance - Quatrosense Environmental Ltd. QEL QTS - 2000.
6="6_23">6.23 Point Type ``GAS2''.1 Description - Carbon monoxide concentration sensor.
.2 Technical Performance - 0 - 125 ppm CO output drift < 2% signal/month.
.3 Standard of Acceptance - Quatrosense Environmental Ltd.
6.24 Point Type ``GAS3''.1 Description - flammable gas concentration sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
6.25 Point Type ``GAS4''.1 Description - Refrigerant vapour concentration sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
6.26 Point Type ``GAS5'' .1 Description - Total
volatile organic compounds (TVOC's) concentration sensor, designed for mounting within an
occupied
space. This type of device is sometimes referred to as an indoor air quality sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
6.27 Point Type ``LS1''.1 Description - Photocell light level sensor, with analogue output related to light intensity.
.2 Technical Performance - Dark 1 meg ohm, bright
1.5 K ohm..3 Standard of Acceptance - Greystone PSR-1.
6.28 Point Type ``LS2''.1 Description - Photocell, adjustable light level switch.
.2 Technical Performance -
.3 Standard of Acceptance -
6.29 Point Type ``OS1''.1 Description - Passive infrared occupancy sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
6.30 Point Type ``OTS''.1 Description - Outside air temperature sensor.
.2 Technical Performance -
10K ohm thermistor sensor encapsulated in a 6 mm OD probe, complete with
weatherproof
enclosure, sun shield and mounting bracket. Operating range: -35 deg C to +50 deg C.
End-to-end
accuracy:
+/-
.3 Standard of Acceptance - Greystone TE-200-F, c/w 100K ohm parallel resistor.
6.31 Point Type ``PS1''.1 Description - Pipe Pressure Transducer
.2 Technical Performance -
Brazed assembly with 300 series stainless steel parts that are in contact with the media,
snap
tract and circuit board c/w external pressure sensor and mounted in a NEMA 4 enclosure.
Accuracy +/-
Inputs - 7.5 - 32 VDC
Range - Suffix A - 350 kPa
.3 Standard of Acceptance - Greystone PGS-100
6.32 Point Type ``PTS1''.1 Description - Pipe Temperature Sensor, immersion type .
.2 Technical Performance -
10K ohm thermistor sensor encapsulated in a 6 mm OD, 50 mm long probe, with screw
fitting
for insertion into a standard thermowell. Sensor assembly to be complete with enclosure
and thermowell.
Operating
range: -10 deg C to 100 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-C
6.33 Point Type ``PTS2''.1 Description - Pipe Temperature Sensor, strap-on type.
.2 Technical Performance -
10K ohm thermistor encapulated in a stainless steel pad designed for strap-on
installation.
Assembly
to be complete with solid-state circuitry in an enclosure and connecting cable to the
thermistor. Operating
range:
-10 deg C to 100 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-E-7
6.34 Point Type ``RHS''.1 Description - Relative Humidity Sensor Room Type.
.2 Technical Performance -
operating range: 10% RH to 90% RH, over a 0 deg C to 60 deg C temperature range.
End-to-end
accuracy: +/-
.3 Standard of Acceptance
- Greystone HS-150-B-02
-
Hy-cal C102-H
.1 Description - Room temperature sensor complete with momentary override switch.
.2 Technical Performance -
Assembly shall consist of a 10K ohm thermistor and related circuitry mounted on a circuit
board/baseplate
for wall mounting, complete with a vented, plastic enclosure. Operating range: 10 deg C to
30 deg
C.
End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-AE-OR
6.36 Point Type ``RTS2''.1 Description - Room Temperature Sensor, security type.
.2 Technical Performance -
Assembly shall consist of a 10K ohm thermistor and related circuitry mounted on a rigid,
metal
cover plate designed for mounting into a recessed junction box. The sensing element shall
be attached directly
to
the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-AS
6.37 Point Type ``RTS3'' .1 Description - Room
temperature sensor complete with momentary override switch, setpoint adjustment, and
setpoint
indication.
.2 Technical Performance -
Assembly shall consist of a 10K ohm thermistor and related circuitry mounted on a rigid,
metal
cover plate designed for mounting into a recessed junction box. The sensing element shall
be attached directly
to
the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance
- Greystone TE-200-IT
-
Delta Intellistat RTS406
.1 Description - Velocity sensor (single point flow sensor).
.2 Technical Performance - 0 - 3000 FPM Adjustable 4'' - 16'' ducts. (Thermal anemometer technology).
.3 Standard of Acceptance - BELIMO.
6.39 Point Type ``VS2'' .1 Description - Air
velocity sensor with thermal anemometer technology, using differential pressure signal
from a flow
grid
in duct or VAV box inlet.
.2 Technical Performance -
.3 Standard of Acceptance -
6.40 Point Type ``WPS'' .1 Description - (Window
Position Switch) Point type ``WPS'' is used to describe a digital input connected to a dry
contact
which is part of a magnetic proximity switch on openable sections of glazing. The dry
contact will be open
when
the window is open, and closed when the window is closed.
.2 If the window supplier
provides the proximity switches, and wiring from their dry contacts, to 300 mm above the
window
head above the openable section, use the CRS designation for the point.
[
Previous Page || Table of Contents || Overview || Section TOC || Next Page ][ Comments || Disclaimer ]