Mnemonic | Mnemonic Description | Examples | ||
---|---|---|---|---|
Sys. | Point | Func. | ||
TR* | . | . | Term Reheat Sys* | TR,TR1 |
. | SF | . | Supply Fan | TR1_SF |
. | RF | . | Return Fan | TR1_RF |
. | EF | . | Exhaust Fan | TR1_EF |
. | SAT | . | Supply Air Temperature | TR1_SAT |
. | RAT | . | Return Air Temperature | TR1_RAT |
. | MAT | . | Mixed Air Temperature | TR1_MAT |
. | SAH | . | Supply Air Humidity | TR1_SAH |
. | RAH | . | Return Air Humidity | TR1_RAH |
. | MAD | . | Mixed Air Dampers | TR1_MAD |
. | OAD | . | Outside Air Dampers | TR1_OAD |
. | EAD | . | Exhaust Air Dampers | TR1_EAD |
. | CCV | . | Cooling Coil Valve | TR1_CCV |
. | CLG | . | Cooling System | TR1_CLG |
. | HCV | . | Heating Coil Valve | TR1_HCV |
. | HTG | . | Heating System | TR1_HTG |
. | PCV | . | Preheat Coil Valve | TR1_PCV |
. | CCP | . | Cooling Coil Pump | TR1_CCP |
. | HCP | . | Heating Coil Pump | TR1_HCP |
. | PCP | . | Preheat Coil Pump | TR1_PCP |
. | DX | . | Direct Expansion Valve | TR1_DX2 |
. | ECP | . | Evaporative Cooling Pump | TR1_ECP |
. | FRZ | . | Freeze Detection | TR1_FRZ |
. | RT | . | Room Temperature | TR1_RT5 |
. | Z*** | . | Zone *** Terminal Equip | TR1_Z8 |
. | |----> | . | Reheat Coil Valve | TR1_Z8_RCV |
. | |----> | . | Room Temperature | TR1_Z8_RT |
. | |----> | . | Perim Rad Valve | TR1_Z8_RAD |
. | |----> | . | Perim Panel Valve | TR1_Z8_PAN |
. | . | S | Status | TR1_PCP_S |
. | . | SP | Setpoint | TR1_SAT_SP |
. | . | CO | Controller | TR1_Z8_CO |
. | . | LL | Low Limit | TR1_MAT_LL |
. | . | TZ | Totalizer | TR1_SF_TZ |
. | . | TL | Trend Log | TR1_TL |
. | . | MODE | Mode | TR1_CLG_MODE |
. | . | PG | Program | TR1_MAD_PG |
. | . | AL | Alarm | TR1_DX2_AL |