| Mnemonic | Mnemonic Description | Examples | ||
|---|---|---|---|---|
| Sys. | Point | Func. | ||
| SZ* | . | . | Single Zone System* | SZ, SZI | 
| . | SF | . | Supply Fan | SZ1_SF | 
| . | RF | . | Return Fan | SZ1_RF | 
| . | EF | . | Exhaust Fan | SZ1_EF | 
| . | SAT | . | Supply Air Temperature | SZ1_SAT | 
| . | RAT | . | Return Air Temperature | SZ1_RAT | 
| . | MAT | . | Mixed Air Temperature | SZ1_MAT | 
| . | SAH | . | Supply Air Humidity | SZ1_SAH | 
| . | RAH | . | Return Air Humidity | SZ1_RAH | 
| . | MAD | . | Mixed Air Dampers | SZ1_MAD | 
| . | OAD | . | Outside Air Dampers | SZ1_OAD | 
| . | EAD | . | Exhaust Air Dampers | SZ1_EAD | 
| . | CCV | . | Cooling Coil Valve | SZ1_CCV | 
| . | CLG | . | Cooling System | SZ1_CLG | 
| . | HCV | . | Heating Coil Valve | SZ1_HCV | 
| . | HTG | . | Heating System | SZ1_HTG | 
| . | PCV | . | Preheat Coil Valve | SZ1_PCV | 
| . | DX | . | Direct Expansion Valve | SZ3_DX2 | 
| . | CCP | . | Cooling Coil Pump | SZ1_CCP | 
| . | HCP | . | Heating Coil Pump | SZ1_HCP | 
| . | PCP | . | Preheat Coil Pump | SZ1_PCP | 
| . | ECP | . | EvaporativeCooling Pump | SZ1_ECP | 
| . | FRZ | . | Freeze Detection | SZ1_FRZ | 
| . | RT | . | Room Temperature | SZ1_RT1 | 
| . | . | S | Status | SZ1_PCP3_S | 
| . | . | SP | Setpoint | SZ1_SAT_SP | 
| . | . | CO | Controller | SZ1_SAT_CO | 
| . | . | HL | High Limit | SZ1_SAT_HL | 
| . | . | LL | Low Limit | SZ1_MAT_LL | 
| . | . | TZ | Totalizer | SZ1_SF_TZ | 
| . | . | TL | Trend Log | SZ1_TL | 
| . | . | MODE | Mode | SZ1_HTG_MODE | 
| . | . | PG | Program | SZ1_PG | 
| . | . | AL | Alarm | SZ1_SAT_AL | 