[ Previous Page || Table of Contents || Overview || Next Page ]


The information displayed here is available as a Microsoft Excel .xls file. Please click on this link to download this file.


BC Buildings Corporation - CCS Point Naming Convention

(HTG) HEATING WATER SYSTEMS

Mnemonic Mnemonic Description Examples
Sys. Sys. Point Func.
HTG . . Heating HTG
RAD . . Radiation System RAD
RHT . . Reheat System RHT
PHT . . Preheat System PHT
PAN . . Radiant Panel System PAN
GLY . . Glychol System GLY
DHW . . Domestic Hot Water System DHW
. SWT . Supply Water Temp RAD_SWT
. RWT . Return Water Temp HTG_RWT
. SWT . Supply Glycol Temp GLY_SWT
. RGT . Return Glycol Temp GLY_RWT
. V . Control Valve PAN_V
. P . Pump DHW_P5
. FS . Flow Swich HTG_FS
. . S Status RAD_P4_S
. . SP Setpoint RHT_SWT_SP
. . CO Controller RAD_SWT_CO
. . TZ Totalizer PHT_P2_TZ
. . TL Trend Log RAD_TL
. . MODE Mode HTG_MODE
. . PG Program DHW_PG
. . AL Alarm RAD_P4_AL

[ Previous Page || Table of Contents || Overview || Next Page ]