BC Buildings Corporation - CCS Point Naming Convention

(HP) HEAT PUMP SYSTEM

Mnemonic Mnemonic Description Examples
Sys. Point Func.
HP* . . Heat Pump System* HP
. CTF . Cooling Tower Fan HP_CTF
. CTP . Cooling Tower Pump HP_CTP
. P . Pump HP_P1
. SWT . Loop Supply Temperature HP_SWT
. RWT . Loop Return Temperature HP_RWT
. CV . Cooling Valve HP_CV
. HV . Heating Valve HP_HV
. BLR . Boiler HP_BLR
.   . Ht.Pump *** Terminal Equip HP216
. |----> C Compressor HP216_C
. |----> F Fan Control HP216_F
. |----> RT Room Temperature HP216_RT
. |----> REV Mode (HTG/CLG) HP216_REV
. |----> SAT Supply Air Temp HP216_SAT
. . S Status HP_P1_S
. . SP Setpoint HP_SWT_SP
. . CO Controller HP_RWT_CO
. . MIN Minimum HP_RT_MIN
. . AVG Average HP_RT_AVG
. . MAX Maximum HP_RT_MAX
. . TZ Totalizer HP_P1_TZ
. . TL Trend Log HP_TL
. . PG Program HP_PG
. . AL Alarm HP_RT_MIN_AL

NOTE: Position of reversing valve will be as per units.
"ie, Point Name = hp216_rev,Units = heat or cool"