Client Comfort System (CCS)
5.1 - BCBC PRE-APPROVED SYSTEM TYPES - (Graphic/Logic/Points
List - One Page Format)
Sections 2,3 and 4 of this manual refer to Section 15930
Systems. The following pages and information in Section 5 and the
Example in Section 10 should
assist in assembly of Section 15930.
Intent
To assist in standardization and improve the communication of
BCBC Client Comfort Systems (CCS) intent to designers, a One Page
concept has been developed for preferred BCBC system types. The
One Page includes the CCS graphic layout, generic start up logic,
and points lists (real and virtual). The format is 11" X
17". When used in standard 8.5" X 11"
documentation the information shall be laid out on opposing pages
to emulate the 11" X 17" format.
Instructions
- 1. The designer will choose the system type that
matches the building. If no match exists the designer
will contact the BCBC representative to discuss the
unique requirements. If deemed necessary a unique system
type will be generated by BCBC in consultation with the
designer.
- 2. This One Page format will become part of the
specification and tendering package. A copy for each
system will be put into the specification with a unique
HVAC system description. This description will become
part of the BCBC naming convention which is imbedded in
the points list. Please use the naming convention when
labeling equipment elsewhere on the plans and in the
specifications.
- 3. Extra points for the system or points generally
required to complete the project will be listed on the
miscellaneous point sheet. A sample is included in
Section 5 of the design manual.
- 4. All computerized color graphics generated by
the successful CCS contractor will follow the BCBC Client
Comfort System Graphics Guidelines. See Section 7 of the
design manual.
- 5. Generic start up logic must be made
syntactically correct by the successful contractor.
- 6. Refer to this manual's Table of Contents to
locate various categories of systems.
- 7. When trendlog (TL) virtual points are part of a
system the points to be trended are listed in the notes.
Points are separated by commas. Eg HCV,SAT_SP,SAT,HCP.
- 8. When controller (CO) virtual points are part of
a system the measured variable is listed first in the
notes and then the setpoint. The two are separated with a
colon. Eg SAT:SAT_SP.
- 9. A Project Summary as per 5_A1 Example and 5_A2
blank sheet will be prepared for each project. Review
example in Section 10 of this manual for further
clarification.