.1 This Clause contains a comprehensive range of field devices listed alphabetically by ``Point type'' code,
not all of which will necessarily be applicable to this project. Refer to the ``Point Type'' column on the
points lists in Section 15930 to identify the devices relevant to this project.2 Some point types have a number as the last character in order to identify variations in a group of similar
field devices. For each separate point type or group of similar devices (common point type except for
number) all items provided shall be the product of one manufacturer..3 All field devices shall be selected to have full compatibility with the SAPs, TUCs or other controls
components being proposed..4 Any field device proposed for use which is not one of the products listed under ``Standard of Acceptance'
will be evaluated by the Owner's representative against the specified technical performance and the quality
and characteristics of the products which are listed. If any proposed field device is deemed not equivalent
to the specification, then the contractor will be given one opportunity to propose another device which does
meet specification at no cost..5 The proposal must include technical data for all field devices listed in the points lists, specifically
cross-referenced to the particular point type to facilitate an unambiguous proposal evaluation..6 Some devices may require different ranges, capacities, etc. in particular applications, even though the device
or component is otherwise the same. Where definition of such variations is required in the specifications or
points lists, the point type will use suffixes, for example ``DPS/x'' or ``DA1/x''. The suffixes are explained in
the ``Technical Performance'' portion of each point type specification..7 The end-to-end accuracy required for analogue devices shall include the combined effect of sensitivity,
hysteresis, linearity and repeatability between the measured variable and the output at the operator interface
device, or between the panel signal to the digital-to-analogue converter and the controlled variable.
.8 Devices shall meet the specific requirements listed, and shall be compatible with respect to power supply,
signal characteristics, or other factors with the CCS being proposed. Power supplies shall be provided as
required for any and all devices.
.1 Description - Control Relay Status ``CRS'' is used where the field device will be either:
- an auxiliary dry contact, supplied as part of the equipment whose status will be monitored by this point,
or
- if there is no auxiliary dry contact on the equipment, a relay as specified in 2. and 3., provided by the
control contractor..2 Technical Performance - a high impedance relay to produce a dry contact.
.3 - Standard of Acceptance - Omron Model GSD
- Veris Model 607 voltage bug.
.1 Description - Control Relay (Solid State)
.2 Technical Performance - 240 V, 10 amp capacity, SPST function. Normally open (or normally closed) as
required by points list or application complete with optical isolation. Suitable for switching inductive AC
loads..3 Standard of Acceptance - Electromatic - RS104240
- Potter & Brumfield EOTZ Series
- Grayhill 7052-04-C-12-S.
.1 Description - Control relay (dry contact electro-mechanical relay).
.2 Technical Performance - 240 V, 10A to suit application.
.3 Standard of Acceptance - IDEC-RH Series
- Johnson R1020 series.
.1 Description - Control relay (Solid state relay suitable for switching D.C. loads).
.2 Technical Performance - 60 VDC.
.3 Standard of Acceptance - Grayhill.
6.7 Point Type ``CS2''.1 Description - Current sensor (analogue).
.2 Technical Performance - Self powered, with insertion impedance loss less than 0.0006 ohms under all
conditions. End-to-end accuracy +/- 2% of full scale at each range. Ranges: 1.0 to 10.0 amps, low;
5 to 50 amps, middle; 20 to 200 amps, high; selectable by switch or by setting jumpers..3 Standard of Acceptance - Greystone CS-150.
6.8 Point Type ``CV1''.1 Description - Current Sensor (switch).
.2 Technical Performance - Solid State N.O. AC switch. Same ranges as point type ``CS1''. Manual
adjustment of switch threshold setting..3 Standard of Acceptance - Greystone CS-125.
6.9 Point Type ``CV2''.1 Description - Control Valve (2 way, 2 position)
.2 Technical Performance - Brass or bronze globe valve construction, with screwed ends. Materials suitable
for chilled water or hot water up to 125 deg C. 24 VAC. Working pressure, 875 kPa. N.O. spring return.
Minimum close off pressure rating shall meet requirements in the points lists; if no requirement, minimum
close off pressure rating shall be 70 kPa..3 Standard of Acceptance - Honeywell V8043 series
- Johnson J-series.4 Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is specified in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that specified.
6.10 Point Type ``CV3''.1 Description - Control Valve (2 way, floating control).
.2 Technical Performance - Brass or bronze body, globe valve with equal percentage flow characteristic,
screwed ends. Materials suitable for chilled water or hot water up to 125 deg C. Working pressure
875 kPa. 24 VAC reversing motor drive. Minimum close off pressure rating shall be 30 psi, or as stated
in the points list, which ever is higher..3 Standard of Acceptance - Johnson
- Honeywell.4 Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is specified in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that specified.
.1 Description - Control Valve (2 way modulating, non-spring-return).
.2 Technical Performance - Globe valve body, with equal percentage flow characteristics. Materials suitable
for chilled water or hot water up to 125 deg C. Modulating actuator with 0-10 VDC signal range, power
to open and power to close. Working pressure 875 kPa.
6.11 Point Type ``CV4''.3 Standard of Acceptance - Johnson
- Honeywell.4 Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is specified in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that specified.
6.10.2..1 Description - Control Valve (2 way, modulating, spring return).
.2 Technical Performance - Technical performance shall be as specified in
.3 Standard of Acceptance
- Johnson
-
Honeywell
.4 Submittal Data - Submittal data shall include the proposed Cv
rating for each control valve. If a specific
Cv is specified in the points list or on a valve
schedule, ensure the control valve proposed has a similar
Cv to that specified.
.1 Description - Damper Actuator (Electric, modulating, non-spring-return).
.2 Technical Performance - Power Voltage 24 VAC or 120 VAC.
- Control Voltage 0 - 10 VDC.
.1 Description - Damper Actuator (Electric, modulating, spring return).
.2 Technical Performance - Power voltage 24 VAC or 120 VAC
- Control Voltage 0 - 10 VDC
6.14 Point Type ``DA3/x''.3 Standard of Acceptance - Belimo FM-24SR (``DA2/A'')
- Belimo AF-24SR (``DA2/C'')
- Johnson Controls M130-GGA (``DA2/A'' only)
.1 Description - Direct Coupled Damper Actuator (Electric, 2-position, non-spring-return).
.2 Technical Performance - Power Voltage 24 VAC or 120 VAC
6.15 Point Type ``DA4/x''.3 Standard of Acceptance - Belimo NM-24 (``DA3/A'')
- Belimo SMC-24 (``DA3/B'')
- Belimo SM-24 (``DA3/C4/'')
.1 Description - Damper Actuator (Electric, 2-position, spring return).
.2 Technical Performance - Power Voltage, 24 VAC or 120 VAC.
Suffixes - ``DA4/A'' - 130 in-lb.
.3 Standard of Acceptance - Belimo SF-24.
- Belimo SF-120.
.1 Description - Point type ``DDC'' is used to describe on analogue output which is to be connected to
a piece of equipment not supplied by the controls contractor for the purpose of controlling that equipment's
operation in some way. Examples would be an output to a variable speed drive to control its speed, or an
output to a modulating chiller (or boiler) to control its operating output..2 The controls contractor shall provide wiring, and interface devices.
.1 Description - Duct mounted relative humidity sensor.
.2 Technical Performance - Operating range, 10% RH to 90% RH, over a 0 deg C to 60 deg C temperature
0.2%
range. End-to-end accuracy +/- 3% of operating range, with maximum temperature dependence of
per deg C change. 200 mm long probe, with enclosure, for mounting in duct..3 Standard of Acceptance - Greystone HS-250-C-02
- Hy-cal CT-829-A
.1 Description - Differential Pressure Sensor
.2 Technical Performance - Solid-state design, operating on capacitance principle, with non-interactive fine
resolution, zero, and span adjustments. End-to-end accuracy +/- 2% of full scale pressure range, including
temperature compensation. Shall have integral filters at each air connection port.
Suffixes - ``DPS/A'' - 0 to 25 PA pressure range.
- ``DPS/B'' - 0 to 50 PA pressure range.
&nbsnbsp; - ``DPS/C'' - 0 to 75 PA pressure range.
- ``DPS/D'' - 0 to 125 PA pressure range.
- ``DPS/E'' - 0 to 250 PA pressure range.
- ``DPS/F'' - 0 to 500 PA pressure range.
- ``DPS/G'' - 0 to 750 PA pressure range.
- ``DPS/H'' - 0 to 1250 PA pressure range.
.1 Description - Duct temperature sensor, with an averaging element.
.2 Technical Performance - Constructed of FT6 plenum rated cable or soft copper tubing, incorporating
0.3 deg C. Assembly complete with
numerous temperature sensors encapsulated at equal distances along the length of the element. The
assembly acts as a single sensor, reporting the average temperature from all the individual sensors.
Operating range: 0 deg C to 60 deg C; end-to-end accuracy +/-
wiring housing and mounting flange.
Suffixes - ``DTS1/A'' -
3.5 m sensor cable length
- ``DTS1/B'' - 6.0 m cable length.3 Standard of Acceptance - Greystone TE-200
- Pre-con
.1 Description - Duct temperature sensor, with probe type element.
.2 Technical Performance - Sensor encapsulated in a 200 mm long, 6 mm OD copper or stainless steel probe.
0.3 deg C. Assembly complete with wiring
Operating range 0 deg C to 60 deg C; end-to-end accuracy +/-
housing and mounting flange.
.3 Standard of Acceptance - Greystone TE-200-B-7-C
- Pre-con
.1 Description - ``Freezestat'' auto-reset , complete with auxiliary dry contact in order to provide a separate
digital input to the DDC system..2 Technical Performance - Range: -10 deg C to 15 deg C; probe length 6 m. Control responds to the lowest
0.3 m of the entire length of the element.
temperature along any.3 Standard of Acceptance - Penn A170-GA-1
.1 Description - CO2 concentration sensor.
.2 Technical Performance - 0 - 2500 ppm +/- 2% Full Scale.
.3 Standard of Acceptance - Quatrosense Environmental Ltd. QEL QTS - 2000.
.1 Description - Carbon monoxide concentration sensor.
.2 Technical Performance - 0 - 125 ppm CO output drift < 2% signal/month.
.3 Standard of Acceptance - Quatrosense Environmental Ltd.
.1 Description - flammable gas concentration sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
.1 Description - Refrigerant vapour concentration sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
.1 Description - Total volatile organic compounds (TVOC's) concentration sensor, designed for mounting
within an occupied space. This type of device is sometimes referred to as an indoor air quality sensor..2 Technical Performance -
.3 Standard of Acceptance -
.1 Description - Photocell light level sensor, with analogue output related to light intensity.
.2 Technical Performance - Dark 1 meg ohm, bright
1.5 K ohm..3 Standard of Acceptance - Greystone PSR-1.
.1 Description - Photocell, adjustable light level switch.
.2 Technical Performance -
.3 Standard of Acceptance -
.1 Description - Passive infrared occupancy sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
.1 Description - Outside air temperature sensor.
.2 Technical Performance - 10 K ohm thermistor sensor encapsulated in a 6 mm OD probe, complete with
0.3 deg C over the entire operating range.
weatherproof enclosure, sun shield and mounting bracket. Operating range: -35 deg C to +50 deg C.
End-to-end accuracy: +/-.3 Standard of Acceptance - Greystone TE-200-F, c/w 100 K ohm parallel resistor.
.1 Description - Pipe Pressure Transducer
.2 Technical Performance - Brazed assembly with 300 series stainless steel parts that are in contact with the
media, snap tract and circuit board c/w external pressure sensor and mounted in a NEMA 4 enclosure.
Accuracy +/- 0.3% span from best fit straight line.
.1 Description - Pipe Temperature Sensor, immersion type .
.2 Technical Performance - 10 K ohm thermistor sensor encapsulated in a 6 mm OD, 50 mm long probe,
0.3 deg C over the
with screw fitting for insertion into a standard thermowell. Sensor assembly to be complete with enclosure
and thermowell. Operating range: -10 deg C to 100 deg C. End-to-end accuracy: +/-
entire operating range..3 Standard of Acceptance - Greystone TE-200-C
.1 Description - Pipe Temperature Sensor, strap-on type.
.2 Technical Performance - 10 K ohm thermistor encapulated in a stainless steel pad designed for strap-on
0.3 deg C over the entire
installation. Assembly to be complete with solid-state circuitry in an enclosure and connecting cable to the
thermistor. Operating range: -10 deg C to 100 deg C. End-to-end accuracy: +/-
operating range..3 Standard of Acceptance - Greystone TE-200-E-7
.1 Description - Relative Humidity Sensor Room Type.
.2 Technical Performance - operating range: 10% RH to 90% RH, over a 0 deg C to 60 deg C temperature
3.0% of operating range, with maximum temperature dependence of 0.2%
range. End-to-end accuracy: +/-
RH per deg C change. Assembly shall be complete with a baseplate for wall mounting, a rigid circuit board
for all circuitry and the sensing element, and a ventilated enclosure..3 Standard of Acceptance - Greystone HS-150-B-02
- Hy-cal C102-H
.1 Description - Room temperature sensor complete with momentary override switch.
.2 Technical Performance - Assembly shall consist of a 10 K ohm thermistor and related circuitry mounted
0.3 deg C over the entire operating range.
on a circuit board/baseplate for wall mounting, complete with a vented, plastic enclosure. Operating range:
10 deg C to 30 deg C. End-to-end accuracy: +/-.3 Standard of Acceptance - Greystone TE-200-AE-OR
.1 Description - Room Temperature Sensor, security type.
.2 Technical Performance - Assembly shall consist of a 10 K ohm thermistor and related circuitry mounted
0.3 deg C over the entire pressure range.
on a rigid, metal cover plate designed for mounting into a recessed junction box. The sensing element shall
be attached directly to the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-AS
.1 Description - Room temperature sensor complete with momentary override switch, setpoint adjustment,
and setpoint indication..2 Technical Performance - Assembly shall consist of a 10 K ohm thermistor and related circuitry mounted
0.3 deg C over the entire pressure range.
on a rigid, metal cover plate designed for mounting into a recessed junction box. The sensing element shall
be attached directly to the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-IT
- Delta Intellistat RTS406
.1 Description - Velocity sensor (single point flow sensor).
.2 Technical Performance - 0 - 3000 FPM Adjustable 4'' - 16'' ducts. (Thermal anemometer technology).
.3 Standard of Acceptance - BELIMO.
.1 Description - Air velocity sensor with thermal anemometer technology, using differential pressure signal
from a flow grid in duct or VAV box inlet..2 Technical Performance -
.3 Standard of Acceptance -
.1 Description - (Window Position Switch) Point type ``WPS'' is used to describe a digital input connected
to a dry contact which is part of a magnetic proximity switch on openable sections of glazing. The dry
contact will be open when the window is open, and closed when the window is closed..2 If the window supplier provides the proximity switches, and wiring from their dry contacts, to 300 mm
above the window head above the openable section, use the CRS designation for the point.
[