.1 This Clause contains a comprehensive range of field
devices listed alphabetically by "Point type" code, not all of
which will necessarily be applicable to this
project. Refer to the "Point Type" column on the points lists in Section
15930 to identify the devices relevant to this
project.
.2 Some point types have a number as the last character in
order to identify variations in a group of similar field
devices. For each separate point type or group of
similar devices (common point type except for number) all items
provided shall be the product of one manufacturer.
.3 All field devices shall be selected to have full
compatibility with the SAPs, TUCs or other controls components
being proposed.
.4 Any field device proposed for use which is not one of the
products listed under "Standard of Acceptance" will be
evaluated by the Corporation's representative against
the specified technical performance and the quality and
characteristics of the products which are listed. If
any proposed field device is deemed not equivalent to the
specification, then the controls contractor shall
provide another device which does meet specification at no extra
cost.
.5 The shop drawing submittal shall include technical data for
all field devices listed in the points lists, specifically
cross-referenced to the particular point type to
facilitate the shop drawing review.
.6 Some devices may require different ranges, capacities, etc.
in particular applications, even though the device or
component is otherwise the same. Where definition of
such variations is required in the specifications or points
lists, the point type will use suffixes, for example
"DPS/x" or "DA1/x". The suffixes are explained in the "Technical
Performance" portion of each point type
specification.
.7 The end-to-end accuracy required for analog devices shall
include the combined effect of sensitivity, hysteresis,
linearity and repeatability between the measured
variable and the output at the operator interface device, or
between the panel signal to the digital-to-analog
converter and the controlled variable.
.8 Devices shall meet the specific requirements listed, and
shall be compatible with respect to power supply, signal
characteristics, or other factors with the CCS being
proposed. Power supplies shall be provided as required for
any and all devices.
.1 Description - Control Relay Status "CRS" is used where the field device will be either:
- an auxiliary dry contact, supplied as part of the equipment whose status will be monitored by this point, or
- if there is no auxiliary dry
contact on the equipment, a relay as specified in 2. and 3., provided by the control
contractor.
.2 Technical Performance - a high impedance relay to produce a dry contact.
.3 Standard of Acceptance - Omron Model GSD, Veris Model 607 voltage bug
.1 Description - Control Relay (Solid State)
.2 Technical
Performance - 240 V, 10 amp capacity. SPST function. Normally open (or normally closed) as
required
by
points list or application complete with optical isolation. Suitable for switching
inductive AC loads.
.3 Standard of
Acceptance - Electromatic - RS104240.
-
Potter & Brumfield EOTZ Series.
-
Grayhill 7052-04-C-12-S.
.1 Description - Control relay (dry contact electro-mechanical relay).
.2 Technical Performance - 240 V, 10 A to suit application.
.3 Standard of
Acceptance - IDEC-RH Series.
- R1020 series.
- Johnson.
.1 Description - Control relay (Solid state relay suitable for switching D.C. loads).
.2 Technical Performance - 60 VDC.
.3 Standard of Acceptance - Grayhill
.1 Description - Current sensor (analogue).
.2 Technical
Performance - Self powered, with insertion impedance
loss less than 0.0006 ohms under all
conditions.
End-to-end accuracy ± 2% of full scale at each range. Ranges: 1.0 to 10.0 amps, low; 5 to
50 amps,
middle;
20 to 200 amps, high; selectable by switch or by setting jumpers.
.3 Standard of Acceptance - Greystone CS-150.
.1 Description - Current Sensor (switch).
.2 Technical
Performance - Solid State N.O. AC switch. Same ranges
as point type "CS1". Manual adjustment
of
switch threshold setting.
.3 Standard of Acceptance - Greystone CS-125.
.1 Description - Control Valve (2 way, 2 position)
.2 Technical
Performance - Brass or bronze globe valve
construction, with screwed ends. Materials suitable for
chilled
water or hot water up to 125°C. 24 VAC. Working pressure, 875 kPa. N.O. spring return.
Minimum
close
off pressure rating shall meet requirements in the points lists; if no requirement,
minimum close off pressure
rating
shall be 70 kPa.
.3 Standard of
Acceptance - Honeywell V8043 series.
-
Johnson J-series
.4 Submittal
Data - Submittal data shall include the proposed Cv
rating for each control valve. If a specific Cv
is
specified in the points list or on a valve schedule, ensure the control valve proposed has
a similar Cv to that
specified.
.1 Description - Control Valve (2 way, floating control).
.2 Technical
Performance - Brass or bronze body, globe valve with equal percentage flow characteristic,
screwed
ends.
Materials suitable for chilled water or hot water up to 125°C. Working pressure 875 kPa.
24 VAC reversing
motor
drive. Minimum close off pressure rating shall be 30 psi, or as stated in the points list,
which ever is higher.
.3 Standard of
Acceptance - Johnson
-
Honeywell
.4 Submittal Data -
Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is
specified
in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that
specified.
.1 Description - Control Valve (2 way modulating, non-spring-return)
.2 Technical
Performance - Globe valve body, with equal percentage flow characteristics. Materials
suitable for
chilled
water or hot water up to 125°C. Modulating actuator with 0-10 VDC signal range, power to
open and
power
to close. Working pressure 875 kPa.
.3 Standard of
Acceptance - Johnson
-
Honeywell
.4 Submittal Data -
Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is
specified
in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that
specified.
.1 Description - Control Valve (2 way, modulating, spring return).
.2 Technical Performance - Technical performance shall be as specified in 6.10.2.
.3 Standard of
Acceptance - Johnson
-
Honeywell
.4 Submittal Data -
Submittal data shall include the proposed Cv rating for each control valve. If a specific
Cv is
specified
in the points list or on a valve schedule, ensure the control valve proposed has a similar
Cv to that
specified.
.1 Description - Direct Coupled Damper Actuator (Electric, modulating, non-spring-return).
.2 Technical
Performance - Power Voltage 24
VAC or 120 VAC.
-
Control Voltage 0 - 10 VDC.
Suffixes:
- "DA1/A" -
50 in-lb torque capacity.
-
"DA1/B" - 90 in-lb
torque capacity.
-
"DA1/C" - 130 in-lb
torque capacity.
.3 Standard of
Acceptance - Belimo NM-24SR or NM-24SRS
("DA1/A")
-
Belimo SMC-24SR ("DA1/B")
-
Belimo SM-24SR or SM-24SRS ("DA1/C")
-
Johnson Controls M140-GGA ("DA1/A")
-
Johnson Controls M150-GGA ("DA1/B" or "DA1/C")
.1 Description - Damper Actuator (Electric, modulating, spring return).
.2 Technical
Performance - Power
voltage 24 VAC or 120 VAC
-
Control Voltage 0 - 10 VDC
Suffixes:
- "DA2/A" -
50 in-lb torque capacity.
-
"DA2/B" - 90
in-lb torque capacity.
-
"DA2/C" - 133
in-lb torque capacity.
.3 Standard of
Acceptance - Belimo FM-24SR, NF-24 SR
("DA2/A")
-
Belimo AF24-SR ("DA2/C")
-
Johnson Controls M130-GGA ("DA2/A" only)
.1 Description - Damper Actuator (Electric, 2-position, non-spring- return).
.2 Technical Performance - Power Voltage 24 VAC or 120 VAC
Suffixes:
- "DA3/A" -
75 in-lb torque capacity.
-
"DA3/B" - 90 in-lb
torque capacity.
-
"DA3/C" - 130 in-lb torque
capacity.
.3 Standard of
Acceptance - Belimo NM-24 ("DA3/A")
-
Belimo SMC-24 ("DA3/B")
-
Belimo SM-24 ("DA3/C4/")
.1 Description - Damper Actuator (Electric, 2-position, spring return).
.2 Technical Performance - Power Voltage, 24 VAC or 120 VAC
Suffixes: - "DA4/A" - 130 in-lb torque capacity.
.3 Standard of Acceptance - Belimo SF-24, AF-24, NF-24, SF-120, AF-120, NF-120.
5.16 Point Type "DDC" .1 Description -
Point type "DDC" is used to describe on analog output which is to be connected
to a piece of
equipment
not supplied by the controls contractor for the purpose of controlling that equipment's
operation in some
way.
Examples would be an output to a variable speed drive to control its speed, or an output
to a modulating
chiller
(or boiler) to control its operating output.
.2 The controls contractor shall provide wiring, and interface devices.
5.17 Point Type "DHS".1 Description - Duct mounted relative humidity sensor.
.2 Technical
Performance - Operating range, 10% RH to 90% RH, over a 0°C to 60°C temperature range.
End-to-end
accuracy ±3% of operating range, with maximum temperature dependence of 0.2% per °C
change.
200
mm long probe, with enclosure, for mounting in duct.
.3 Standard of
Acceptance - Greystone
HS-250-C-02
-
Hy-cal CT-829-A
.1 Description - Differential Pressure Sensor
.2 Technical
Performance - Solid-state design, operating on capacitance principle, with non-interactive
fine resolution,
zero,
and span adjustments. End-to-end accuracy ±2% of full scale pressure range, including
temperature
compensation.
Shall have integral filters at each air connection port.
Suffixes:
- "DPS/A" -
0 to 25 Pa pressure range.
-
"DPS/B" -
0 to 50 Pa pressure range.
-
"DPS/C" -
0 to 75 Pa pressure range.
-
"DPS/D" -
0 to 125 Pa pressure range.
-
"DPS/E" -
0 to 250 Pa pressure range.
-
"DPS/F" -
0 to 500 Pa pressure range.
-
"DPS/G" -
0 to 750 Pa pressure range.
-
"DPS/H" -
0 to 1250 Pa pressure range.
.3 Standard of
Acceptance - Modus T20-xxx, T30-xxx, or T40-xxx
to suit pressure range and application.
-
Autotran 700.
.1 Description - Duct temperature sensor, with an averaging element.
.2 Technical
Performance - Constructed of FT6 plenum rated cable or soft copper tubing, incorporating
numerous
temperature
sensors encapsulated at equal distances along the length of the element. The assembly acts
as a single
sensor,
reporting the average temperature from all the individual sensors. Operating range:
0°C to 60°C.
End-to-end
accuracy ±0.3°C. Assembly complete with wiring housing and mounting flange.
Suffixes:
- "DTS1/A" -
3.5 m sensor cable length
-
"DTS1/B" -
6.0 m cable length
.3 Standard of
Acceptance - Greystone TE-200
-
Pre-con
.1 Description - Duct temperature sensor, with probe type element.
.2 Technical
Performance - Sensor encapsulated in a 200 mm long, 6 mm OD copper or stainless steel
probe.
Operating
range 0°C to 60°C. End-to-end accuracy ±0.3°C. Assembly complete with wiring
housing and
mounting
flange.
.3 Standard of
Acceptance - Greystone
TE-200-B-7-C
-
Pre-con
.1 Description - Electro-pneumatic transducer.
.2 Technical
Performance - The electro-pneumatic transducer receives a 0-10 VDC or 0-20 mA signal
input, and
produces
a 3-15 psig pneumatic output signal to position damper and valve actuators. The device
shall come
complete
with a pneumatic output pressure gauge.
.3 Standard of
Acceptance - Greystone EPT8500
-
Delta EPT750
.1 Description -
"Freezestat" auto-reset , complete with auxiliary dry contact in order to
provide a separate digital
input
to the DDC system.
.2 Technical
Performance - Range: -10°C to 15°C; probe length 6 m. Control responds to the lowest
temperature
along
any 0.3 m of the entire length of the element.
.3 Standard of Acceptance - Penn A170-GA-1
5.23 Point Type "GAS1".1 Description - CO2 concentration sensor.
.2 Technical Performance - 0 - 2500 ppm ±2% Full Scale.
.3 Standard of Acceptance - Quatrosense Environmental Ltd. QEL QTS - 2000.
5.24 Point Type "GAS2".1 Description - Carbon monoxide concentration sensor.
.2 Technical Performance - 0 - 125 ppm CO output drift <2% signal per month.
.3 Standard of Acceptance - Quatrosense Environmental Ltd.
5.25 Point Type "GAS3".1
Description - flammable gas concentration sensor..2
Technical Performance.3
Standard of Acceptance 5.26 Point Type "GAS4".1
Description - Refrigerant vapour concentration sensor..2
Technical Performance.3
Standard of Acceptance 5.27 Point Type "GAS5".1
Description - Total volatile organic compounds (TVOC's) concentration sensor, designed for mounting within an.2
Technical Performance.3
Standard of Acceptance.1 Description - Photocell light level sensor, with analogue output related to light intensity.
.2
Technical Performance - Dark 1 meg ohm, bright 1.5 K ohm..3
Standard of Acceptance - Greystone PSR-1..1 Description - Photocell, adjustable light level switch.
.2
Technical Performance.3
Standard of Acceptance.1 Description - Passive infrared occupancy sensor.
.2
Technical Performance.3
Standard of Acceptance.1 Description - Outside air temperature sensor.
.2
Technical Performance - 10K ohm thermistor sensor encapsulated in a 6 mm OD probe, complete with.3
Standard of Acceptance - Greystone TE-200-F, c/w 100 K ohm parallel resistor..1 Description -Pipe Pressure Transducer.
.2 Technical
Performance - Brazed assembly with 300 series stainless steel parts
that are in contact with the media,
snap
tract and circuit board c/w external pressure sensor and mounted in a NEMA 4 enclosure.
Accuracy ±3%
span
from best fit straight line.
Inputs
- 7.5 - 32 VDC, outputs - 4 - 20 ma or 1-5 VDC.
Range
- Suffix A - 0 - 350 kPa - Suffix B - 0 - 700 kPa
.3 Standard of Acceptance - Greystone PGS - 100
.1 Description - Pipe Temperature Sensor, immersion type .
.2 Technical
Performance - 10K ohm thermistor sensor encapsulated in a 6 mm OD, 50
mm long probe, with screw
fitting
for insertion into a standard thermowell. Sensor assembly to be complete with enclosure
and thermowell.
Operating range: -10°C to 100°C. End-to-end
accuracy: ±0.3°C over the entire operating range.
.3 Standard of Acceptance - Greystone TE-200-C
.1 Description - Pipe Temperature Sensor, strap-on type.
.2 Technical
Performance - 10K ohm thermistor encapulated in a stainless steel pad
designed for strap-on installation.
Assembly
to be complete with solid-state circuitry in an enclosure and connecting cable to the
thermistor.
 bsp; Operating range: -10°C to 100°C. End-to-end accuracy:
±0.3°C over the entire operating range.
.3 Standard of Acceptance - Greystone TE-200-E-7
.1 Description - Relative Humidity Sensor Room Type.
.2 Technical
Performance - Operating range: 10% RH to 90% RH, over a 0°C to 60°C
temperature range.
End-to-end accuracy: ±3.0% of operating range, with maximum temperature
dependence of 0.2% RH per °C
change.
Assembly shall be complete with a baseplate for wall mounting, a rigid circuit board for
all circuitry and the
sensing
element, and a ventilated enclosure.
.3 Standard
of Acceptance -
Greystone HS-150-B-02
- Hy-cal C102-H
.1 Description - Room temperature sensor complete with momentary override switch.
.2 Technical
Performance - Assembly shall consist of a 10K ohm thermistor and
related circuitry mounted on a circuit
board/baseplate
for wall mounting, complete with a vented, plastic enclosure. Operating
range: 10°C to 30°C.
End-to-end accuracy: ±0.3°C over the entire operating range.
.3 Standard of Acceptance - Greystone TE-200-AE-OR
.1 Description - Room Temperature Sensor, security type.
.2 Technical
Performance - Assembly shall consist of a 10K ohm thermistor and
related circuitry mounted on a rigid,
metal
cover plate designed for mounting into a recessed junction box. The sensing element shall
be attached directly
to
the cover plate. Operating range: 10°C to 30°C. End-to-end
accuracy: ±0.3°C over the entire pressure range.
.3 Standard of Acceptance - Greystone TE-200-AS
.2 Technical
Performance - Assembly shall consist of a 10K ohm thermistor and
related circuitry mounted on a rigid,
metal
cover plate designed for mounting into a recessed junction box. The sensing element shall
be attached directly
to
the cover plate. Operating range: 10°C to 30°C. End-to-end
accuracy: ±0.3°C over the entire pressure range.
.3 Standard
of Acceptance -
Greystone TE-200-IT
- Delta Intellistat RTS406
.1 Description - Velocity sensor (single point flow sensor).
.2 Technical Performance - 0 - 3000 FPM Adjustable 4" - 16" ducts. (Thermal anemometer technology).
.3 Standard of Acceptance - BELIMO.
[