The information displayed here is available as a Microsoft Word .doc file. Please click on this link to down load this file.
15900 | Controls General |
---|---|
All controls are referred to as the Client Comfort System (CCS). All controls shall be computerized direct digital except where noted in the following specification. | |
15910 | Scope of Work |
Provide a Client Comfort System, as specified in this document, for the Example Building. CCS shall be accessed remotely via modem. The operating system of the CCS shall operate in Windows 3.1 or higher, and shall coexist with other vendor's systems, presently operating in Windows, to provide a multi-vendor work station at the BCBC Property Management Unit Office. | |
15920 | Job Specific Alterations to BCBC Performance Specifications |
No communication computers will be provided for the project. Communication will be via modem with existing computer at the Property Management Unit. Contractor shall make the CCS operating system operational on this computer and demonstrate remote communication to system. Computer will meet Corporation hardware and set up standards and will have at least 10 MB of disk space. | |
15925 | Smoke/Fire Sequence |
The vollowing smoke sequences shall be incorporated in the Client Comfort System. When fire alarm system is activated both VAV1 and VAV2 shall shut down via a hardware connection to the fire panel. If the fire department activates a particualr fan system for smoke removal, a smoke override switch on the fire panel shall restore power to the fan control circuits and a smoke override VAV1 SOKE1-ovr or smoke override VAV2 SMOKE2_OVR relay shall be turned on. These are two separate digital inputs to the CCS connected to the smoke relays on the fire panel. These points are shown as part of the CCS on the Miscellaneous Point Sheet. The following smoke sequence shall be added to the Generic Start Up Code for VAV1 (BCBC Variable Volume Type L) and VAV2 (BCBC Variable Volume Type A). VAV1 modify 2.2 to read: The following smoke sequence shall be added to the Generic Start Up Code for BCBC Variable Air Volume TUC (Type V-A) and (Type V-N).
| |
EXAMPLE |
[ Comments || Disclaimer
]